UtilitySaver Burner Control
Benefits
- Minimum Fuel Usage
- Maximum Electrical Savings
- Improved Availability with Full Speed Bypass
- Real Time Boiler Efficiency Display
- New or Existing Flame Safety System interface
The UtilitySaver combines the fuel savings of an Oxygen trim system with the electrical kWh savings of a variable speed drive (VSD) FD fan. The UtilitySaver is intended for installation on an existing burner with either a jackshaft or parallel positioning combustion control system.
Typical Energy Savings
- ASME "by losses" boiler efficiency calculations
- Industry leading manufacturer motor energy data
- 600 Bhp boiler
- 125 psi steam
- Natural gas fired
- Operating 365 days/year & 24 hours/day
- Electric cost - 7.7 cents/kWh
- Fuel cost - $4.5/k ft3
- Oxygen reduction - 1.5% wet
Minimum Fuel Usage
- Flue gas Oxygen is used to continuously adjust (trim) the fuel/air ratio
- Oxygen trim saves fuel by fine tuning the burner to operate safely and reliably at reduced excess air levels throughout the burner firing range
Minimum Fan Power Usage
- Fan speed control minimizes damper pressure drop related fan power usage
Maximum Electrical Savings
- UtilitySaver maximizes VSD electrical energy savings by keeping the FD fan damper(s) 100% open from high fire down to approximately 30% firing rate (field adjustable)
- From 30% firing rate down to minimum fire, the damper ramps from full open to partially closed to assure maximum burner turndown is achieved
Improved Availability with Full Speed Bypass
- “Flip-a-Switch” to change over from variable speed to constant speed control with pre-set full speed air damper curve
Real Time Boiler Efficiency Display
- Allows the boiler operator to instantly identify inefficiencies and potential operational problems
Direct Interface
- Directly Interfaces with 135 ohm or 4-20 mAdc Boiler or Plant Master firing rate controllers
- Optional transmitter adds local PID firing rate control
Safety
- Flue gas temperature and Oxygen are monitored
- Low flue gas Oxygen trips the burner after an adjustable time delay
- VSD speed and actuator position feedbacks are continuously monitored and the burner trips if any are out of position
New or Existing Flame Safety System Interface
- It permits automatic operation at a reduced cost of installation
Features
- Manual air trim capability with automatic adaptive gain
- Integral Oxygen Analyzer diagnostics provides continuous cell impedance checking for cell health prediction
- Oxygen trim delayed after light-off (adjustable) to allow stack oxygen to stabilize
- Simple Auto/Manual station on the front of the controller to allow automatic or manual control of the burner firing rate
- Light off position is adjustable for wide turndown burners
- Fuel-air lead/lag to provide low CO (gas) and smokeless (oil) load changes. The air increases before the fuel on a load increase, and the fuel decreases before the air on a load decrease
- Easy commissioning using “Learn Mode”
- Automated purge & light-off under flame safeguard system direction. VSD "at speed" contact interlocks burner purge and light-off limits
- RS485 Modbus interface is available for off-site monitoring and control
Commissioning
The PC3_Setup Commissioning Software is included with every UtilitySaver Burner Control:
- MS Windows compatible
- Automated step-by-step procedure to assist the service technician with the setup of the fuel and air actuators, ZP oxygen sensor, VSD, and fuel/air profile
- Software is only required during commissioning, calibration and tuning
- User friendly interface Content

PC3_Setup Main Menu
When Task 5 is selected and the "Run" button is "pressed", the
screens to the right are shown

PC3_Setup Sample User Prompts
Input verification and equipment calibration is automated to
ensure a thorough and fast burner setup
PC3_Setup Air/Fuel Profile Setup Screen
A Single Screen is provided to enter setup data and inspect the resulting fuel/air profile
Specifications

UtilitySaver Panel Enclosure |
|
|
Controller: Input Power: Actuator Power: Enclosure: |
PCC-III-ZG00 (Click here for a complete hardware specifications) 120 Vac (+/- 15%) 24 Vac 16h x 14w x 10d NEMA 12, wall mounted |
Inputs |
|
|
Drum Pressure*: Flue Gas Temperature: Flue Gas Oxygen: Plant Master: Fuel Actuator Feedback: Air Actuator Feedback: VSD Speed Feedback: |
4-20 mAdc (optional) T/C ZP Probe 4-20 mAdc Potentiometer Potentiometer 4-20 mAdc |
Outputs |
|
|
Boiler Efficiency: Fuel Valve Actuator: Air Damper Actuator: VSD Speed Demand: |
4-20 mAdc Triac Triac 4-20 mAdc |
In-Situ Oxygen Sensor, Model ZP |
|
|
Insertion Length: Flange: Mounting Kit (190680): |
20, 30, 45, 65, 90" Probe 3" 125 lb flanges, nipple, coupling, gasket, bolts, nuts and washers, calibration tubing, compression fittings and isolation valve |
Signal Cable Kit (190681) |
|
|
ZP Cable: T/C Cable: Triac Output Cable: Load Sensor Cable: |
70 ft of 7 conductor wire cable for ZP probe 70 ft of type J T/C shielded cable 100 ft of 3 wire shielded cable 50 ft of 2 wire shielded cable |
Boiler Efficiency Kit (104087D) |
|
|
Efficiency: T/C: |
ASME “by losses” method efficiency configuration Flue Gas Temperature Assembly, 104087D, with mounting flange |
| Actuators | |
|
Fuel: Air: Mounting Kit (190682): |
DM-1E-P1A-S2 DM-1E-P1A-S2 Right angle mounting bracket for Damper Actuator, (3) Lever Arms, (4) ball joints, (2) 12" threaded Links |
Note: When "ST" or "HW" ooption selected, Pressure shown, Temperature for Hot Water Applications
Standard Equipment
- UL Labeled, Wired and Tested Control Panel
- PCC-III-ZG00 UtilitySaver Controller
- 24Vac Actuator Power Supply
- VSD – FSG Interface Relays
- ZP-20 Oxygen Probe
- ZP Oxygen Probe Mounting Kit
- Flue Gas T/C Assembly
- Air Damper Actuator
- Air Damper Mounting Kit
- Fuel Valve Actuator
- Variable Speed Drive
- VSD Fuses
- Field Wiring Kit
- Instruction Manual
Optional Equipment
- VSD Full Speed Bypass
- Pressure Transmitter
- Temperature Transmitter
Ordering Information
Variable Speed Drive (VSD) Ordering Information
| Order Sensors Separately (Optional) |
Catalog Number |
|---|---|
| Hot Water Temperature Transmitter, 4-20 mAdc, 0 to 500 F, NEMA 4, Smart with 4.5" depth |
Consult Factory |
| Steam Pressure Transmitter, 4-20 mAdc, 0 to 200 psi, NEMA 4, Smart with single valve manifold |
Consult Factory |
| Thermowell, SS, 4.5" x 1/2 NPT | Consult Factory |