Steam Modulating Lead/Lag
Features
- 2 to 10 Modulating Boilers
- Warm Standby
- "Base Load Auto-Shift"
The Chief Dispatcher Model JC-CDST optimizes steam system performance and helps extend Cast Iron Sectional, Finned-Tube, Fire Box, Flexible Tube or Firetube boiler life.

2 to 10 Modulating Boilers
- Boiler firing rates are automatically adjusted to satisfy the overall plant steam heating load using accurate PID control
- When desired, the Operator may set the firing rate manually
Warm Standby
- Each off-line boiler is periodically started and held at low fire until it returns to the Warm Standby Temperature
- This feature helps minimize thermal shock on the boiler when called on-line
"Base Load Auto-Shift"
- Lag boilers are “Base Loaded” for efficiency, but will increase or decrease the firing rate to “Help” the Lead Boiler. This method minimizes boiler on/off cycling due to short term load swings while maximizing total boiler plant efficiency
- “Unison” modulating can be field selected (all boilers fire at the same rates)
10 Boiler Controller Front Panel Shown
Panel Details |
|
|
Controller: Case Size: Enclosure Type: |
PWC (Click here for a complete hardware specifications) 19¼" H X 18" W X 8½" D Wall mounted, Weight: 55 lbs. |
Inputs |
|
|
Steam Pressure: BAS, Boiler Disable: Boiler Lockout: Warm Standby: |
0 to 25 psi, 0 to 200 psi, or 0 to 500 psi, 4-20 mAdc 24 Vdc 120 Vac, optically isolated (each boiler) 120 Vac, optically isolated (each boiler) 120 Vac, optically isolated (each boiler) |
Outputs |
|
|
Modulation: Boiler Start: |
Isolated 4-20 mAdc or 0-135 ohm (each boiler) Dry contact, 8FLA, ½ HP, 120 Vac (each boiler) |
Optional Features |
Catalog Number |
|---|---|
| Historical Trending | 190604 |
| Telephone Modem | 190603 |
Order Sensors Separately (Quantity as Required) |
Catalog Number |
| Steam Pressure Sensor 0-25 psi with syphon loop |
70600 |
| Steam Pressure Sensor 0-200 psi with syphon loop |
70601 |
| Steam Pressure Sensor 0-500 psi with syphon loop |
70602 |