Hot Water with Boiler Pump Modulating Lead/Lag
Features
- 2 to 7 Fully Modulating Boilers
- Boiler Pump Sequencing
- Domestic Hot Water Priority
The Chief Dispatcher Model JC-CDHWBP optimizes hot water system performance and helps extend Cast Iron Sectional, Finned-Tube, Fire Box or Flexible Tube boiler life. Boiler pump sequencing ensures accurate temperature sensing and boiler cool down.

2-7 Fully Modulating Boilers
- Hot water supply header temperature is maintained using accurate PID control
- “Unison” boiler modulation to ensure even heat delivery
- Lag boilers are brought up to the “Unison” firing rate using a predetermined Ramp Rate to meet the heating load with minimum overshoot
- When desired, the operator may set the “Unison” firing rate manually
Boiler Pump Sequencing
- It keeps the lead boiler pump running to ensure accurate header temperature sensing
- Provides pump shutdown delay for boiler cool down
Outdoor Reset
- Saves energy by lowering supply header temperature setpoint as the outside air temp increases
- Operating cost is reduced during warmer days
- Hot water supply setpoint may be set manually
Time of Day / Week Setback
- Saves energy by lowering supply header temperature setpoint during times when heating requirement is reduced, such as at night or on weekends and holidays
Domestic Hot Water Priority
- A temperature switch will override any setpoint input and force the header supply temperature setpoint to a Domestic Hot Water Setpoint
- A relay output is available to start a domestic hot water pump if required
Condensing Boiler Logic
- Maximizes the number of boilers running near low fire to maximize efficiency
5 Boiler Controller Front Panel Shown
Panel Details |
|
Controller: Case Size: Enclosure Type: |
PWC (Click here for a complete hardware specifications) 19¼" H X 18" W X 8½" D Wall mounted, Weight: 55 lbs. |
Inputs |
|
Hot Water Header: Outdoor Air: BAS Reset Setpoint: BAS Boiler Disable: Limits: Boiler Lockout: Domestic HW Priority: |
0 to 300° F, Thermistor Thermistor (non “-BAS” version) 4-20 mAdc (“-BAS” version) 120 Vac, optically isolated 120 Vac, optically isolated (each boiler) 120 Vac, optically isolated (each boiler) 120 Vac, optically isolated |
Outputs |
|
Modulation: Boiler Start: Pump Start: Domestic HW Circulation Pump: |
Isolated 4-20 mAdc or 0-135 ohm (each boiler) Dry contact, 8FLA, ½ HP, 120 Vac (each boiler) Dry contact, 8FLA, ½ HP, 120 Vac (each boiler) Dry contact, 8FLA, ½ HP, 120 Vac |
| Optional Features | Catalog Number |
|---|---|
| Historical Trending | 190604 |
| Telephone Modem | 190603 |
| Building Automation System (BAS) | add "-BAS" suffix |
| Condensing Boiler Logic | add "-C" suffix | Order Sensors Separately (Quantity as Required) | Catalog Number |
| Hot Water Thermistor Temperature Sensor 0 to 300F, 4 1/2" depth |
70610 |
| Thermowell, SS, 4 1/2" x 1/2" NPT | 70610W |
| Outside Air Thermistor Temperature Sensor with weatherproof cover |
70612 |