Flame Safeguard System

BurnerMate TS

The BurnerMate Model BM-FSG Flame Safeguard System provides automatic flame safety monitoring and control for new or existing steam or hot water boilers. The system is engineered to be in compliance with the latest Factory Mutual and NFPA 85 standards. The systems are manufactured, tested and labeled according to UL508A standards.

[Technical Information]

 

 

  • Microprocessor-based Controller
    • The Flame Safeguard system is microprocessor-based, with self-diagnostics and non-volatile memory
  • Flame Scanners
    • An infrared (IR) flame scanner is provided as a standard for water-wall furnaces
    • An ultrviolet (UV) self checking flame scanner is an available option for refractory lined furnaces
    • The Flame Safeguard System provides the proper burner sequencing, ignition and flame monitoring protection on single burner, automatically ignited oil or gas fired boilers.
  • Fail-safe "de-energize" design
    • The system uses a fail-safe "de-energize" to trip design
    • Upon the loss of system power, the fuel safety shutoff valves are automatically closed and ignition components are de-energized
  • Message Display
    • An externally-mounted LCD backlit display has two lines of sixteen characters each
    • The display provides burner status and historical information
    • Operation, troubleshooting and maintenance information is at the boiler front, where it is needed
    • On a safety shutdown, the message display will advise the operator that the contorl is in "Lockout" and will indicate the specific cause and the state in the operationg sequence where the shutdown occurred
  • Combustion Control Sequence Interlocks
    • Combustion control system interfaces are provided to sensure safe automatic fuel and air sequencing for purge, light-off and shutdown
  • Drum level conductivity probe relays
    • The relays are incorporated for an auxiliary Low Water Cutout safety interlock, Low Water Alarm and High Water Alarm
Operator Control Panel

Display:

Pushbutton

2 line x 16 character LCD Display

Membrane, tactile feedback

IR Flame Scanner

IR Flame Scanner

Infrared, 1/2" 90 degree angle mount, 96" cable

UV Flame Scanner

UV Flame Scanner

Ultraviolet 1" NPT Mount, 72" Lead

Optional Features Add Suffix to
BurnerMate Catalog
Number
Flame Safeguard Add "-FSG" suffix