Parallel Positioning Boiler Control

[Technical Information]

Steam Parallel positioning system

Steam System

  • Steam drum pressure is maintained using local PID setpoint control
  • Minimum fuel usage – Flue gas oxygen is used to continuously adjust (trim) the fuel/air ratio
  • Minimum fan power usage – Fan speed control minimizes damper pressure drop related to fan power usage
  • Real time boiler efficiency display to allow the boiler operator to instantly identify inefficiencies and potential operational problems
  • Safety – Flue gas temperature and Oxygen are monitored.  Warning alarms and burner safety shutdown interlocks are available. VSD speed and actuator position feedbacks are continuously monitored and the burner trips if any are out of position.

HW Parallel positioning

Hot Water System

  • Hot water temperature is maintained using local PID setpoint control
  • Minimum fuel usage – Flue gas oxygen is used to continuously adjust (trim) the fuel/air ratio
  • Minimum fan power usage – Fan speed control minimizes damper pressure drop related to fan power usage
  • Real time boiler efficiency display to allow the boiler operator to instantly identify inefficiencies and potential operational problems
  • Safety – Flue gas temperature and Oxygen are monitored.  Warning alarms and burner safety shutdown interlocks are available. VSD speed and actuator position feedbacks are continuously monitored and the burner trips if any are out of position.

Specifications

BurnerMate Panel

Controller:

Input Power:

PCC-III-GZS0

120 Vac (+/- 15%)

Inputs

Drum Pressure / Water Temperature:

Flue Gas Temperature:

Flue Gas Oxygen:

Plant Master:

Fuel Gas Actuator Feedback:

Fuel Oil Actuator Feedback:

Air Actuator Feedback:

VSD Speed Feedback:

4-20 mAdc

T/C (Option “-ZP”)

ZP Probe (Option “-ZP”)

4-20 mAdc*

Potentiometer*

Potentiometer*

Potentiometer

4-20 mAdc (Option “-VSD”)

Outputs

Boiler Efficiency:

Fuel Gas Valve Actuator:

Fuel Oil Valve Actuator:

Air Damper Actuator:

VSD Speed Demand:

4-20 mAdc

Triac*

Triac*

Triac

4-20 mAdc (Optional “-VSD”)

*These features are standard, but their use is selectable at time of start-up.

Ordering Information

Steam System

Description Catalog Number
Steam Boiler Control BM-STPPT
Order Sensors Separately
(Optional)
Catalog Number
Steam Pressure Transmitter, 4-20 mAdc,
0 to 200 psi, NEMA 4, Smart with single
valve manifold
Consult
Factory

Hot Water

Description Catalog Number
Hot Water Boiler Control BM-HWPPT
Order Sensors Separately
(Optional)
Catalog Number
Hot Water Transmitter, 4-20 mAdc.
0 to 500 F, NEMA 4, with 4.5" depth
Consult
Factory
Thermowell, SS, 4.5" x 1/2 NPT Consult
Factory

Additional Ordering Information

  1. Specify Model ZP In-Situ Oxygen Sensor
  2. Specify Variable Speed Drive (VSD)
  3. Specify Rotary Actuator
  4. Consult factory for low fire change over, VSD bypass or pnuematic actuators