Smoke Opacity Monitor
Features
- Automatic Calibration when Burner cycles off
- Early warning Message and Relay Contact
- Burner Safety Shutdown Message and Relay Contact
- High Visibility Bargraph and numeric display
- Three Alarm sequences (field selectable)
The Preferred Instruments JC-30D Smoke Opacity Monitoring System assures an accurate measurement of the smoke emissions from boilers, incinerators, kilns, and similar sources of intermittent, visible emissions. The system provides a continuous opacity readout, alarm indication and shutdown capability.
Automatic Calibration when Burner Cycles off
- The JC-30D includes a 120 Vac input that monitors the burner fan starter coil and initiates an Automatic Calibration cycle whenever the burner fan stops running (ensuring a clear stack condition). This prevents nuisance burner trips due to dust build-up
- “WARNING: CLEAN LENSES NOW” is displayed when the dust level is high
- At the completion of the Calibration Cycle, the JC-30D turns off the light source until the fan re-starts, extending the life of the bulb
- A Calibration Cycle can be manually initiated from the JC-30D Menu
Early Warning Message and Relay Contact
- Deteriorating combustion conditions can be detected early before developing into major problems
Burner Safety Shutdown Message and Relay Contact
- Dangerously high opacity is an indication of an unstable flame condition
Optical Sensing Assembly
- The Optical Sensing Assembly consists of a Light Source and Light Sensor
- These units are mounted on opposite sides of the smoke duct with the light beam focused from the source side to the sensor side
- This reliable single pass design requires no moving parts or complicated optical devices
- Lenses are specially designed for easy cleaning without dismantling the installed assembly
Three Alarm Sequences (field selectable)
- Standard – This is the most used sequence with a 20 seconds “smoke-puff” delay and a 120 seconds (adjustable) shutdown relay.
- NYC BAR – This sequence is similar to the Standard Sequence, but conforms to the New York City D.E.P. Bureau of Air Resources requirements.
- Wood / Coal Overfire Air Fan – This sequence is used with stoker fired boilers
Flexible Communications for Data Logging
- 4-20 mAdc Opacity Re-transmission
- RS485 Modbus Interface

The Optical Sensing Assembly consists of a Light Source and Light Sensor. This reliable single pass design requires no moving parts or complicated optical devices. The following are the sensor's operationg sequence:
- Units are mounted on opposite sides of the smoke duct with the light beam focused from the source side to the sensor side
- Smoke passing through the light beam reduces the intensity being received by the sensor
- A signal is transmitted to the indicating instrument which continuously displays the percent smoke opacity and provides the alarm and control function

Panel |
|
| Power Supply: Case Size: Enclosure Type: Ambient Temp.: Digital: Status Messages: Alarm Setpoints: |
120Vac 50/60Hz, 15VA 8"H x 3.5"W x 7.5"D NEMA 4 faceplate, Flush Mounting +32° to +122° F ambient High Contrast LCD Display, 4" high, 0.5% Resolution Bargraph ALARM, SHUTDOWN, WARNING: CLEAN LENSES NOW, EXCESS LIGHT Adjustable 5-50% |
Light Source and Light Sensor |
|
| Calibration: Spectral Response: Angle of Projection: Operational Error: Span Drift: Zero Drift: Calibration Error: Response Time: Sighting Distance: Wiring Distance: Sensor Housing: |
Automatic, Off-Line Photopic Peak and mean within 500-600nm <5° <5% <2% <2% <1% (Linearity) <10 seconds for 95% change in opacity 1 to 8 foot smoke duct, 3 to 10 foot optical path length 500 ft. max (16 ga. wire), 250 ft. max (20 ga. wire) ¾" pipe mount |
Outputs |
|
| Relay Outputs: Output: Network Output: |
Two SPDT Relays, 10 A resistive, 8 FLA, ½ HP, 120 Vac Retransmission 4-20 mAdc, 650 ohm load max 1200-38400 baud, RS485 Modbus, ASCII or RTU |
Ordering Information
- JC-30D includes Monitor, 190711 Light Source and 190712 Light Sensor
Optional Accessories
- Pressure cap set with purge and non-purge fittings (107226P)
- Pressure cap set with integral blower (2 blowers) (190275A)
- Light Sensor shield (for installations with high ambient light levels) (190713)
- Remote audible / visual alarm (SDA-VB)
- Alarm bell, 6" dia., 85 dB (SDA-B6)
- Recorder-31 day, 2 ¼" strip chart (R88-E5)